Separator Medium Filters

Material Overview

  • Fine fibre ensures that filter maintains its efficiency throughout its life in the system
  • Suitable for variable airflow
  • High dust holding capacity Robust design

Application

  • Built-up filter banks, rooftops, split systems, free-standing units, package systems and air handlers

Standard

  • ASHRAE 52.2:2017 : MERV 11 – 14
  • EN779:2012 : M6 – F8
  • Filter Depth (Inches) : 12″
  • Media Type : Glass Fibre
  • Frame Material : Galvanized Steel, Aluminum, MDF, Plywood
  • Separator Style : Aluminum
  • Header Type : Single Flange, Box Type
  • Rec. Final Resistance : 350 Pa
  • Max Operating Temperature : 90°C

Introduction

Model Nominal Size
Inches
(H x W x D)
Actual Size
mm
(H x W x D)
Header
Type
Rated Airflow
(CMH)
Rated Initial
Resistance
(Pa)
M6 Classfication (MERV 11)
BA 12 x 24 x 12 289 x 593 x 292 Box 1,700 110
24 x 24 x 12 593 x 593 x 292 3,400
12 x 24 x 12 289 x 593 x 292 Single 1,700
24 x 24 x 12 593 x 593 x 292 3,400
F7 Classfication (MERV 13)
BA 12 x 24 x 12 289 x 593 x 292 Box 1,700 150
24 x 24 x 12 593 x 593 x 292 3,400
12 x 24 x 12 289 x 593 x 292 Single 1,700
24 x 24 x 12 593 x 593 x 292 3,400
F8 Classfication (MERV 14)
BA 12 x 24 x 12 289 x 593 x 292 Box 1,700 160
24 x 24 x 12 593 x 593 x 292 3,400
12 x 24 x 12 289 x 593 x 292 Single 1,700
24 x 24 x 12 593 x 593 x 292 3,400

* Other dimensions are available on request *

Initial Resistance vs. Airflow (24″x24″x12″)